BS6173:2020
The Gas Interlock System must be CE marked.
A gas interlock system is required to be fitted within every new commercial kitchen which has been built since 2001 or has had any major refurbishment since the release of BS6173:2001.
There are a couple of different ways which a gas interlock system can check that the ventilation is in operation. Firstly, air pressure differential switches can be fitted in the ducting and will physical check for airflow before allowing the gas solenoid valve to open. Alternatively, a more modern method is to use current monitors which will check for a power supply going to the fan and control the gas solenoid valve accordingly. If either at start-up, or during the course of the operation, the fans fail or are turned off the gas solenoid valve will automatically close.
Another aspect of BS6173:2009 is gas pressure proving. The standard states if any of the catering equipment does not have a flame failure device a gas pressure proving system should be installed. A gas pressure proving system will check for any leaks on the pipework or on the appliances at start-up, in the event where a gas leak is detected then this will not allow the gas solenoid valve to open.
The majority of appliances which have been built within the last 10 years should have flame failure devices fitted, however in a kitchen where every appliances does have flame failure devices fitted then gas proving is often still recommended to carry out a gas check on the line and ensure the safety of kitchen staff in the area.
IGEM UP/19
It states gas should not be available within the commercial kitchen if the ventilation is not in operation, and this should be controlled by a gas interlock system. IGEM/UP19 once again states that the gas interlock system can check the ventilation using either air pressure differential switch or current monitors.
IGEM/UP19 does clarify a number of things which are listed in BS6173:2009 however it makes a lot more references to carbon dioxide monitoring within a commercial kitchen. CO2 Monitors should be considered within a commercial kitchen, which hasn’t had any major refurbishment, and there is no gas interlock system is fitted as a means of indicating to staff when the carbon dioxide is increasing and to notify them that they should increase the ventilation within the area.
Also, IGEM/UP19 states that a carbon dioxide monitor should be fitted when there is a variable speed controller to control the ventilation. Where variable speed controllers are fitted the end user has the ability to have all the gas appliances in operation but just trickle the ventilation at a low speed and therefore the CO2 is likely to increase. The CO2 Monitor should alarm at first and second stage, the first stage warning staff at 2800ppm to let them know that they should increase ventilation. In the event where the CO2 continues to rise and the ventilation is not increased, once the CO2 Monitor reaches 5000ppm then (where applicable) the gas solenoid valve shut be closed.
Positioning of the CO2 Monitors within the commercial kitchen is included within DW172 – Edition 2.
DW/172
DW/172 was revised in January 2018 in order to reflect current legislations and the latest cooking techniques and design of catering equipment, by all sections of the catering industry.
The sections that have been modified and amended are –
- The appliance coefficient schedule has been significantly expanded and modified
- Modification to Grease Separation
- The lighting section has been modernised
- New section for Solid Fuel Equipment
- New section for Demand Controlled Kitchen Ventilation Systems
- Gas Interlocking
- Modifications to Pollution Control
- New Section for Recirculation Systems
- Modifications to Cleaning and Maintenance
- Control Panels