Air PD Switch (20-300PA)

SKU: Air PD Category:
  • Comes with 1 metre ducting tube and probe.
  • Adjustable sensitivity to help work with every fan.
  • Simple 2 core back to any Merlin Gas Interlock System.
  • Easy Installation.

Description

We only supply the highest quality air pressure differential switches for increased longevity and reliability, they measure between 20-300Pa. Electrical connections are made by use of two-core cable. Incorporated in each Merlin Gas Interlock system is a 10 seconds Airflow dropout delay. In the event of interruptions to airflow for less than 10 seconds the delay will allow the gas solenoid valve to remain open, preventing nuisance tripping. Should the airflow be interrupted for 10 seconds or more the fan fault LED will illuminate and the gas solenoid valve will close.

Specification
ELECTRICAL MECHANICAL
Contact 1 snap-action pole change over contacts Max Pressure 75 mbar (< 75 °C); 50 mbar (> 75 °C)
Switch Capacity 5 (0.8) A, 250Vac Diaphragm Silicon
Differential Fixed Housing PA / ABS / POM
ENVIRONMENTAL PROTECTION
Working Temperature -30 ~ +85 °C Protection Rating IP54
Storage Temperature -30 ~ +85 °C