Merlin Water Detection Panel

  • Achieves one credit from BREEAM WAT 03
  • Timer & programmable clock built in
  • Two stage monitoring for occupied and unoccupied buildings
  • BMS output available
  • 2 zone input for reading 2x water meters (boundary and incoming)
  • Volt free normally closed input for emergency stop buttons, fire alarm & security systems
  • Remote sounder strobe output
  • 230VAC & 24VDC outputs for water solenoid valves

Description

The Merlin WDP is a water leak monitoring system that has been specifically designed to help achieve the requirements of 2018: 1.0 BREEAM UK New construction (non-domestic buildings).

The WDP system will allow designers, M&E contractors and developers to achieve the ‘Credit’ available to reduce the impact of water leaks that may otherwise go undetected.

All the leak detection water meters and solenoid valves are WRAS-approved.

The system is designed to monitor water flowing through a pulse water meter. If the volume of water reaches the pre-set limit (customer adjustable) the system can isolate the mains water pipe, therefore limiting the amount of water and leak damage.

TECHNICAL SPECIFICATION
CONSTRUCTION USER INTERFACE
Length x Width x Height 140 x 190 x 62mm Display 4.3” Touch Screen
Weight 0.9kg Language English
Housing Material ABS UL-94 V1 Audible Buzzer >70dB @ 1m
POWER SUPPLY RELAY OUTPUTS
Nominal AC Input Voltage 240V AC BMS Relay (Volt Free) 8A, 250V AC
Frequency 50-60Hz Water Valve 100-240V AC
Inrush Current 700mA Water Valve (DC) 1A Max @ 24V DC
Internal Fuse 3.15A @ 250V AC Sound / Strobe 1A Max @ 24V DC
Maximum Power Consumption Normal State <12W / Alarm Condition 12W
ENVIRONMENTAL TYPICAL CABLE CHARACTERISTICS
Operating Temperature -10 ~ 50°C AC Power I/O 1.5 – 2.5mm² Tinned Copper. 1A 100-250V~. Wire Stripping Length 6-7mm
Storage Temperature 0 ~ 40°C BMS Relay 1.5 – 2.5mm² Tinned Copper. 10A 100-250V~. Wire Stripping Length 6-7mm
Humidity RH < 90% (non-condensing) Other #1.0-2.5mm² Tinned Copper. For field connections use wires suitable for ≥60°C
Altitude Rating 2000m
Overvoltage Category II
Pollution Degree 2
Equipment Class 2
Ingress Protection IP6X
COMPLIANCE
Safety EN 61010-1:2010 +A1:2019
EMC EN 61326-1:2021